CAPACITY | 10.0kW | |||
Set | FDT100AVNAWVH | |||
Indoor | FDT100VH | |||
Outdoor | FDCA100VNA-W | |||
Power Source (Outdoor Unit) | 1 Phase 240V 50Hz | |||
*Operation Data
|
Nominal Capacity (Range)
|
Cooling T1 |
kW
|
10.0 (4.0-11.2) |
Heating H1 | 11.2 (4.0-12.5) | |||
Heating H2 | 10 | |||
Power Consumption
|
Cooling T1 | 2.73 | ||
Heating H1 | 2.54 | |||
Maximum Power Consumption | 6.4 | |||
Running Current
|
Cooling T1 |
A
|
13.2 | |
Heating H1 | 12.4 | |||
Inrush Current, Maximum Current | 5, 24 | |||
EER | Cooling T1 | 3.66 | ||
COP | Heating H1 | 4.41 | ||
Sound Power Level (JIS C9612) | Outdoor |
dB(A)
|
69 | |
Sound Pressure Level (JIS C9612)
|
Indoor | P-Hi:47 Hi:39 Me:36 Lo:30 | ||
Outdoor | 54 | |||
External dimensions (HXWXD)
|
Indoor |
mm
|
298x840x840 | |
Panel | 35x950x950 T-PSAE-5BW-E (Fine Snow) / T-PSAE-5BB-E (Shadow Black) | |||
Outdoor | 845x970x370 | |||
Net weight
|
Indoor |
kg
|
Unit 25 Panel 5 | |
Outdoor | 77 | |||
Airflow
|
Cooling (Indoor) |
l/s
|
P-Hi: 616 Hi:433
Me: 383 Lo:283 |
|
Heating (Indoor) | ||||
Installation Data
|
Refrigerant (R32)
|
Quantity | kg | 3.3 |
Pre-Charged to Pipe | m | 30 | ||
Refrigerant Piping
|
Liquid Line |
mm
|
Ø9.52 | |
Gas Line | Ø15.88 | |||
Connection Method | Flare Connection | |||
Maximum Pipe Length (One Way) |
m
|
50 | ||
Max Vertical Height Diff. Between O.U. and I.U. | 50 ( O.U. above I.U. ) / 15 ( O.U. below I.U. ) | |||
Controller | RC-E5, RC-EXZ3A, RCH-E3 or RCN-T-5BW-E2 (Fine Snow) / RCN-T-5BB-E2 (Shadow Black) | |||
Motion Sensor (Optional) | LB-T-5BW-E (Fine Snow) / LB-T-5BB-E (Shadow Black) | |||
Demand Response (AS4755) | Yes | |||
Outdoor air temperature (upper, lower limits)
|
Cooling |
oC
|
-15 to 50 | |
Heating | -20 to 20 |