Mitsubishi Electric Lossnay LGH-100RVX3-E – 278 L/s Heat Recovery Ventilation

SKU: LGH-100RVX3-E / PZ-62DR-EB

Mitsubishi Electric Lossnay LGH-100RVX3-E – 278 L/s Heat Recovery Ventilation
Includes Indoor LGH-100RVX3-E | Includes a Lossnay Wired 7 Day Controller PZ-62DR-EB
Lossnay Ventilation Mode | Filter (Supplied) | Energy efficient
1  Year Manufacturer’s Warranty



MODEL LGH-100RVX3-E
25% (Default speed 1)
Air Volume
m3 /h 250
l/s 69
External Static Pressure Pa 12
Temperature Exchange Efficiency
Heating % 83.5
Cooling % 82.5
Enthalpy Exchange Efficiency
Heating % 75.5
Cooling % 71.5
Specific Fan Power W/(l/s) 0.39
Input Power W 27
Sound Pressure Level dB(A) 18.5
50% (Default speed 2)
Air Volume
m3 /h 500
l/s 139
External Static Pressure Pa 48
Temperature Exchange Efficiency
Heating % 79.5
Cooling % 77
Enthalpy Exchange Efficiency
Heating % 68.5
Cooling % 64
Specific Fan Power W/(l/s) 0.6
Input Power W 83
Sound Pressure Level dB(A) 27
75% (Default speed 3)
Air Volume
m3 /h 750
l/s 208
External Static Pressure Pa 107
Temperature Exchange Efficiency
Heating % 77
Cooling % 72
Enthalpy Exchange Efficiency
Heating % 63
Cooling % 59
Specific Fan Power W/(l/s) 1.01
Input Power W 210
Sound Pressure Level dB(A) 35
100% (Default speed 4)
Air Volume
m3 /h 1000
l/s 278
External Static Pressure Pa 190
Temperature Exchange Efficiency
Heating % 75.5
Cooling % 67.5
Enthalpy Exchange Efficiency
Heating % 60.5
Cooling % 53.5
Specific Fan Power W/(l/s) 1.58
Input Power W 438
Sound Pressure Level dB(A) 40
DUCT SIZE mm 250
WEIGHT kg 53
DIMENSIONS WXDXH mm 1144 x 1231 x 404
ELECTRICAL POWER SUPPLY 220-240V, 50Hz
Maximum Current A 3.77
FUSE RATING (BS88) – HRC (A) A 6
HEAT EXCHANGER Paper with specially treated Cellulose Membrane
STANDARD FILTER ISO 16890 Coarse 60%*
  • Bypass Ventilation ModeStale room air is discharged to outside without passing through the Lossnay core. In spring and autumn when air conditioning is not necessary, the unit operates in bypass ventilation mode.Heat recovery ventilationHeat is recovered from the outgoing stale air. This heat is utilised to pre-heat incoming fresh air so your heating system is not required to work as hard to maintain desired room temperature.

    Lossnay Ventilation Mode

    Room air is discharged to outside via Lossnay core. Heat exchanged outside air is supplied to the room. In summer and winter, air conditioning energy can be recovered by Lossnay unit.

    Filter (Supplied)

    Filter cuts pollen and dust for fresh clean air. Replacement part no. P-220F-E. (G3 grade Classification :EN779:2012)

    High Efficiency Supply Air filter (Optional)

    The supply filter can be upgraded to the high efficency option, a non-washable high efficiency filter (M6 grade Classification :EN779:2012)

    Night Purge (Requires PZ-61DR-E controller)

    During the summer season, the Night Purge mode draws cooler outside air into the room at night. This energy conservation mode reduces the load when the air conditioning is started up the next morning. With new models, it is possible to manually engage and set the night purge operation.

    Simultaneous air supply and exhaust

    Lossnay is the ultimate home ventilation system that provides fresh clean air from outside, while removing both moisture and stale indoor air at the same time. Bringing in fresh air into the house can help improve air quality by lowering the amount of CO2.

    • Air volume 42 l/s (model 15) to 556 l/s (model 200)
    • Clean, fresh air
    • Energy efficient heat recovery
    • Simultaneous air supply and exhaust stale air
    • Heat recovery ventilation
    • Use with Mr Slim and City Multi systems
    • Fresh air without windows open
    • Retains heat
    • Washable supply air filter

Mitsubishi Electric Lossnay LGH-100RVX3-E – 278 L/s Heat Recovery Ventilation – Brochure

Description

278 l/s

Lossnay Ventilation Mode | Filter Included | Energy efficient

air conditioning enquiry