Capacity | 12.5kW | ||
Model Name
|
Indoor Unit | S-1014PU3E | |
Outdoor Unit | U-125PZ3R5 | ||
Panel | Standard type:CZ-KPU3H ECONAVI type:CZ-KPU3A | ||
Cooling capacity Heating capacity
|
kW | 12.5 (3.2 – 13.5) 12.5 (3.3 – 15.0) |
|
BTU/h | 42,700 (10,900 – 46,100) 42,700 (11,300 – 51,200) |
||
EER : COP | W/W | 3.58 : 4.43 | |
COP@H2 condition | W/W | 2.88 | |
Total power input Cooling : Heating | kW | 3.49 : 2.82 | |
TCSPF : HSPF
|
Residential
|
Hot Climate | 5.27 : 5.56 |
Average Climate | 4.73 : 4.87 | ||
Cold Climate | 4.85 : 4.17 | ||
Commercial
|
Hot Climate | 5.84 : 5.51 | |
Average Climate | 6.29 : 5.11 | ||
Cold Climate | 6.95 : 4.53 | ||
Indoor Unit | |||
Power source
|
Phase/Hz | 1 Phase / 50Hz | |
V | 230V | 240V | ||
Dimensions H × W × D
|
Indoor | mm | 319 x 840 x 840 |
Panel | mm | 33.5 x 950 x 950 | |
Net weight Indoor / Panel | kg | 25 / 5 | |
Air volume (H/M/L) Cooling : Heating | L/s | 617 / 450 / 317 : 617 / 450 / 317 | |
Sound pressure level (H/M/L) Cooling : Heating | dB(A) | 46 / 39 / 33 : 46 / 39 / 33 | |
Sound power level (H/M/L) Cooling : Heating | dB | 61 / 54 / 48 : 61 / 54 / 48 | |
Number of fan speeds | 5 | ||
Drain pipe size | mm | VP-25 | |
Outdoor Unit | |||
Power source
|
Phase/Hz | 1 Phase / 50Hz | |
V | 230V | 240V | ||
Current (rated) Cooling : Heating | A | 16.1 : 13.0 | 15.4 : 12.5 | |
Dimensions H × W × D | mm | 996 x 980 x 370 | |
Net weight | kg | 87 | |
Air volume Cooling : Heating | m³/min | 1,369 : 1,336 | |
Sound pressure level (Silent mode) Cooling : Heating | dB(A) | 55 (53) : 55 (53) | |
Sound power level (Silent mode) Cooling : Heating | dB | 73 (71) : 73 (71) | |
Piping connections Liquid / Gas | mm | Ø9.52 / Ø15.88 | |
Pipe length range min. – max. | m | 5 – 50 | |
Elevation difference (OU located lower, OU located higher) | m | 15, 30 | |
Maximum chargeless length | m | 30 | |
Refrigerant at shipping, Additional gas amount | g | R32 2,800 / 45 (g/m) | |
Operation ranges Cooling : Heating | ˚C | -10 to 46 : -15 to 24 |