MODEL | LGH-200RVX3-E | ||
25% (Default speed 1)
|
Air Volume
|
m3 /h | 500 |
l/s | 139 | ||
External Static Pressure | Pa | 11 | |
Temperature Exchange Efficiency
|
Heating % | 83.5 | |
Cooling % | 82.5 | ||
Enthalpy Exchange Efficiency
|
Heating % | 76 | |
Cooling % | 70 | ||
Specific Fan Power | W/(l/s) | 0.41 | |
Input Power | W | 57 | |
Sound Pressure Level | dB(A) | 18 | |
50% (Default speed 2)
|
Air Volume
|
m3 /h | 1000 |
l/s | 278 | ||
External Static Pressure | Pa | 43 | |
Temperature Exchange Efficiency
|
Heating % | 79.5 | |
Cooling % | 76 | ||
Enthalpy Exchange Efficiency
|
Heating % | 67.5 | |
Cooling % | 64.5 | ||
Specific Fan Power | W/(l/s) | 0.59 | |
Input Power | W | 163 | |
Sound Pressure Level | dB(A) | 27.5 | |
75% (Default speed 3)
|
Air Volume
|
m3 /h | 1500 |
l/s | 417 | ||
External Static Pressure | Pa | 96 | |
Temperature Exchange Efficiency
|
Heating % | 77.5 | |
Cooling % | 71.5 | ||
Enthalpy Exchange Efficiency
|
Heating % | 64 | |
Cooling % | 59.5 | ||
Specific Fan Power | W/(l/s) | 1 | |
Input Power | W | 416 | |
Sound Pressure Level | dB(A) | 36 | |
100% (Default speed 4)
|
Air Volume
|
m3 /h | 2000 |
l/s | 556 | ||
External Static Pressure | Pa | 170 | |
Temperature Exchange Efficiency
|
Heating % | 76.5 | |
Cooling % | 66.5 | ||
Enthalpy Exchange Efficiency
|
Heating % | 60.5 | |
Cooling % | 57 | ||
Specific Fan Power | W/(l/s) | 1.54 | |
Input Power | W | 855 | |
Sound Pressure Level | dB(A) | 41.5 | |
DUCT SIZE | mm | (SA,RA)250 (OA,EA)270 x 700 | |
WEIGHT | kg | 108 | |
DIMENSIONS WXDXH | mm | 1144 x 1231 x 808 | |
ELECTRICAL POWER SUPPLY | 220-240V, 50Hz | ||
Maximum Current | A | 5.4 | |
FUSE RATING (BS88) – HRC (A) | A | 10 | |
HEAT EXCHANGER | Paper with specially treated Cellulose Membrane | ||
STANDARD FILTER | ISO 16890 Coarse 60%* |