HP | 12HP | |
unit | RAS-120HNCELW | |
Power supply (Outdoor) | V/Ph/Hz | 380-415V/3Ph/50Hz, 380V/3Ph/60Hz (R: 220V/3Ph/60Hz) |
Capacity
|
Cooling kW | 33.5 |
Heating kW | 37.5 | |
Power Input
|
Cooling kW | 9.64 |
Heating kW | 10.55 | |
Efficiency
|
EER | 3.48 |
COP | 3.55 | |
Max. Current | 415V/3Ph/50Hz A | 27 |
Dimensions | H×W×D mm | 1650×1190×420 |
Net Weight | kg | 203 |
Outdoor Unit Colour | Natural Gray (1.0Y 85/0.5) | |
Footprint Area | m2 | 0.53 |
Compressor type | Inverter Scroll | |
Refrigerant
|
Type | R410A |
Initial Charge Amount kg | 7.7 | |
Number of Fan Motors | 2 | |
External Static | Pressure of Fan Pa | 0/30/60 |
Capacity Ratio of IDU/ODU | 50% – 130% | |
Sound Pressure Level
|
GB Standard (Anechoic), Cooling dB(A) | 59 |
GB Standard (Anechoic), Heating dB(A) | 62 | |
Main Piping Size
|
Liquid (φ)mm | 12.70 |
Gas (φ)mm | 25.40 | |
Connectable IDU Numbe
|
Recommended | 10 |
Maximum | 16 | |
Working Temp. Range (*5)
|
Cooling °C DB | -5 ~ 48 (/52) |
°C WB | (-20/) -15 ~ 16 | |
Maximum Piping Length (*6)
|
Total m | 500 (300) |
From Piping connection kit 1 to Furthest IDU m | 120/150 (Actual/Equivalent) | |
Between Outdoor Units m | 10 | |
Between 1st branch and the furthest IDU m | 90 (40) | |
Between each branch and each IDU m | 40 (30) | |
Maximum Height Difference (*7)
|
Between ODUs m | 0.1 |
Between ODU and IDU (ODU above IDU) m | 50 | |
(IDU above ODU) m | 40 | |
Between IDUs m | 30 |