Daikin VAM1500GJVE 416.7L/s ERV

SKU: VAM1500GJVE 416.7L/s ERV

VAM-GJVE series are compact, energy-efficient, and can operate under a wide outdoor operating temperature range.  These units provide high enthalpy efficiency due to the greatly enhanced performance of the thin film element.




> > > Compare
MODEL VAM1500GJVE
Power Supply 1-phase, 220-240 V/220 V, 50 Hz/60 Hz
 

Temp. Exchange Efficiency

Ultra-High  

 

%

72
High 72
Low 75.5
 

 

 

Enthalpy Exchange Efficiency

 

 

For Heating

Ultra-High  

 

%

65
High 65
Low 67
 

 

For Cooling

Ultra-High  

 

%

61
High 61
Low 64
 

 

 

Power Consumption

 

Heat Exchange Mode

Ultra-High  

 

W

1,145
High 991
Low 835
 

Bypass Mode

Ultra-High  

 

W

1,145
High 991
Low 835
 

 

 

 

Sound Level

Heat Exchange Mode Ultra-High  

 

dB(A)

39.5-41.5
High 37.5-39.5
Low 35-37.5
 

Bypass Mode

Ultra-High  

 

dB(A)

41-43
High 39.5-41
Low 36.5-38
Casing Galvanised steel plate
Insulation Material Self-extinguishable polyurethane foam
Dimensions (HXWXD) mm 785X1,619X832
Machine Weigh kg 129
Heat Exchange System Air to air cross flow total heat (Sensible heat + latent heat) exchange
Heat Exchange Element Material Specially processed nonflammable paper
Air Filter Multidirectional fibrous fleeces
 

 

 

 

 

 

 

 

Fan

Type Sirocco fan
 

 

 

 

Airflow Rate

Ultra-High  

 

m3/h

1,500
High 1,500
Low 1,320
Ultra-High  

 

/s

416
High 416
Low 366
 

External Static Pressure

Ultra-High  

 

Pa

112
High 73
Low 56
Motor Output kW 0.280X4
Connection Duct Diameter mm 350
Unit Ambient Condition -15℃–50℃DB, 80%RH or less

Click to view the Brochure of Daikin Heat Reclaim Ventilator Systems

Description

Daikin HRV unit with an airflow of 416.7L/s (1500m3/h).

air conditioning enquiry