Model Number (Reverse Cycle)
|
Indoor Unit | S035ILR |
Outdoor Unit | S035OVR | |
Rated Cooling
|
Total Capacity (kW)3 | 34.13 |
Sensible3 | 28.12 | |
EER (kW/ikW)3 | 3.44 | |
Rated Heating1
|
Total Capacity (kW) | 33.6 |
COP | 3.78 | |
MEPS Certified | Yes | |
Operating Range
|
Maximum °C | 50 |
Minimum °C | -10 | |
Capacity Steps | % | 0/50/100 |
Compressor
|
Type | Scroll |
Starter | D.O.L (Optional Soft Starter) | |
Qty | 2 | |
Outdoor Fan
|
Type | Hybrid Axial |
Speed Control | Pressure Transducer | |
Qty | 2 | |
Refrigerant System
|
Type | R410A |
Charge Per Circuit kg | 5.7 | |
No of Circuits | 2 | |
Indoor Fan
|
Type | EC Plug |
Speed Control | Potentiometer | |
Qty | 2 | |
Airflow Indoor (L/s)
|
Nominal | 1750 |
Maximum | 2188 | |
Minimum | 1313 | |
Available External Static Pressure |
Pa | High Static Capability (See Fan Performance Curves) |
IP Rating | IP44 | |
Power Supply | (Volt/Phase/Hz) | 400-415V / 3Ph + N / 50Hz |
Rated Load Amps4 | Outdoor/Indoor/ Total |
18/1.2/19.1 |
Full Load Amps5 | Outdoor/Indoor/ Total |
27.2/5.2/32.4 |
Outdoor Dimensions (mm)
|
Height | 1190 |
Width | 1850 | |
Length | 1425 | |
Indoor Dimensions (mm)
|
Height | 690 |
Width | 1700 | |
Length | 820 | |
Indoor and Outdoor Pipe Connection Diameter
|
Liquid mm (inch) | 9.5 (3/8″) x 2 |
Gas mm (inch) | 19.1 (3/4″) x 2 | |
Nominal Weight 2. | Outdoor kg | 389 |
Nominal Weight 2. | Indoor kg | 200 |
Rated Sound Power
|
db(A)
|
66.5
|
1. For reverse cycle model only
2. For base model only. Factory options will vary
3. Performance excludes ikW of evaporator fan motor
4. R.L.A – Run Load Amps are based on current drawn at nominal conditions
5. F.L.A – Full Load Amps are based on the overload settings [max current] of all compressor and fan motor(s)