Three Phase | ||
PKV180T-T | ||
1 Total (Gross) Capacity (kW) (AS/NZS3823.1.2) | Cooling | 16.40 |
Heating | 16.60 | |
Nett (Rated) Capacity (kW) (AS/NZS3823.1.2) | Cooling (min-max) | 16.00 (6.40 – 18.00) |
Heating (min-max) | 17.00 (7.14 – 19.00) | |
Input Power (kW) (AS/NZS3823.1.2) | Cooling | 4.96 |
Heating | 4.85 | |
2 EER Rated (AS/NZS3823.1.2)
3 COP Rated (AS/NZS3823.1.2) |
Cooling | 3.23 |
Heating | 3.51 | |
Power Supply – (V / Ph / Hz) | 400V / 3Ph + N / 50Hz | |
Rated Amps (AS/NZS3823.1.2) | 9.8 | |
Full Load Amps (AS/NZS3823.1.2) | 14.5 | |
4 Circuit Breaker Amps (Suggested) | 20.0 | |
IP Rating | IP44 | |
Compressor | Type / No. per Unit | Tru-Inverter Variable Speed Scroll / 1 |
Starting Method | Inbuilt Soft Starting | |
No. of refrigeration Circuits / No. Capacity Stages (Capacity range) | 1 / Variable Capacity (40-100%) | |
Refrigerant | R-410A | |
Fans (Type x Number per unit) | Outdoor | Axial / 6 Pole External Rotor / Direct Drive x 2 |
Indoor | Twin Deck Centrifugal EC Fan / ECM Direct Drive x 1 | |
Airflow Range Indoor (l/s) |
Maximum | 1020 |
Nominal | 850 | |
Minimum | 680 | |
External Static Pressure (Pa)@Hi | Maximum Airflow | 69 |
Nominal Airflow | 216 | |
Unit Dimensions (mm) |
Depth | 1250 |
Height | 1120 | |
Width | 1490 | |
5 Nominal Weight (kgs) | 267 | |
6 Sound Pressure Level (dBA)
7 Sound Power Level (dBA) |
Outdoor (low/high fan) | 50.0 / 53.0 |
Outdoor (low/high fan) | 69.3 / 72.1 | |
MEPS Compliant | Yes | |
8 Demand Response Capability (AS4755.3) | Capable |
ActronAir PKV180T-T 16.4kW Variable Speed Commercial Packaged Unit 3 Phase
ActronAir PKV180T-T 16.4kW Variable Speed Commercial Packaged Unit 3 Phase
» Tru-Inverter Variable Speed Scroll or Digital Scroll | 25mm foil faced insulation on indoor unit to improve efficiency.
Smart Fan Control technology, Low ambient cooling option down to +5°C
To view the Brochure
Click here
Description
16.40 kW Cooling