MODEL | VAM250GJVE | ||||
Power Supply | 1-phase, 220-240 V/220 V, 50 Hz/60 Hz | ||||
Temp. Exchange Efficiency |
Ultra-High |
% |
75 | ||
High | 75 | ||||
Low | 79 | ||||
Enthalpy Exchange Efficiency |
For Heating |
Ultra-High |
% |
71 | |
High | 71 | ||||
Low | 74 | ||||
For Cooling |
Ultra-High |
% |
63 | ||
High | 63 | ||||
Low | 66 | ||||
Power Consumption |
Heat Exchange Mode |
Ultra-High |
W |
137 | |
High | 120 | ||||
Low | 60 | ||||
Bypass Mode |
Ultra-High |
W |
137 | ||
High | 120 | ||||
Low | 60 | ||||
Sound Level |
Heat Exchange Mode | Ultra-High |
dB(A) |
27-29 | |
High | 26-27.5 | ||||
Low | 21-22 | ||||
Bypass Mode |
Ultra-High |
dB(A) |
28.5-30.5 | ||
High | 27.5-29 | ||||
Low | 22.5-23 | ||||
Casing | Galvanised steel plate | ||||
Insulation Material | Self-extinguishable polyurethane foam | ||||
Dimensions (HXWXD) | mm | 278X810X551 | |||
Machine Weigh | kg | 24 | |||
Heat Exchange System | Air to air cross flow total heat (Sensible heat + latent heat) exchange | ||||
Heat Exchange Element Material | Specially processed nonflammable paper | ||||
Air Filter | Multidirectional fibrous fleeces | ||||
Fan |
Type | Sirocco fan | |||
Airflow Rate |
Ultra-High |
m3/h |
250 | ||
High | 250 | ||||
Low | 155 | ||||
Ultra-High |
/s |
69 | |||
High | 69 | ||||
Low | 43 | ||||
External Static Pressure |
Ultra-High |
Pa |
70 | ||
High | 54 | ||||
Low | 24 | ||||
Motor Output | kW | 0.030X2 | |||
Connection Duct Diameter | mm | 150 | |||
Unit Ambient Condition | -15℃–50℃DB, 80%RH or less |
Daikin VAM250GJVE 69.4L/s ERV
VAM-GJVE series are compact, energy-efficient, and can operate under a wide outdoor operating temperature range. These units provide high enthalpy efficiency due to the greatly enhanced performance of the thin film element.
Click to view the Brochure of Daikin Heat Reclaim Ventilator Systems
Description
Daikin HRV unit with an airflow of 69.4L/s (250m3/hour).