Indoor Unit (845-211-001) | ISD 211LYX |
Outdoor Unit (846-211-003) | OSA 211RLTFH |
Cooling capacity range (gross) | 9.4 ~ 25.3 kW |
Cooling capacity (net) to AS/NZS 3823 T1 | 19.0 |
Heating capacity range | 8.4 ~ 25.6 kW |
Heating capacity H1 | 20.8 kW |
Electrical input – cooling | 6.0 kW |
Electrical input – heating | 5.8 kW |
EER / AEER (cooling) | 3.15 / 3.13 |
COP / ACOP (heating) | 3.57 / 3.54 |
Unit Controllers | UC8 / IUC |
Refrigerant | R32 |
Refrigerant precharge for 15 m | 5.2 kg |
Minimum floor area (@2.4m below ceiling diffuser) | 14.4 m2 |
Additional charge req’d for over 15 m | 60 g/m |
Maximum line length | 60 m |
Max. charge / Min. floor area (below ceiling diffuser) | 7.9 kg / 33.2 m2 |
Separation limit: OSA above ISD | 20 m |
Separation limit: OSA below ISD | 20 m |
Suction line | 19 mm OD |
Liquid line | 9.5 mm OD |
Compressor oil type | POE-46 (NXG5020 or equivalent) |
Additional oil charge over 40 m length | 10 ml/m |
Compressor type | inverter scroll |
Power supply via OSA | 3 ph. 400V ac 50Hz |
Compressor (3ph.) run amps at rating cond. | 9.0 A |
Indoor fan motor size | 1250 W |
Rated indoor fan speed | 6.5 V |
Indoor fan motor (1ph.) – full load | 6 A |
Outdoor fan motor (1ph.) – full load | 1 A (x2) |
Outdoor fan capacitor size | 5 µfd (x2) |
Control circuit breaker (internal) | 10 A |
Running amps (total system) | 13.0 / 9.0 / 10.0 A |
Max. running amps (total system) | 23.0 / 14.5 / 15.5 A |
RCD type recommended | type B, 30mA |
Net weight ISD / OSA | 86 / 129 kg |
Temperzone ISD 211LYX-S1 / OSA 211RLTFH-S1 UC8 + EEV 19.5kW Ducted Air Conditioner System Three Phase
Temperzone ISD 211LYX-S1 / OSA 211RLTFH-S1 UC8 + EEV 19.5kW Ducted Air Conditioner System Three Phase
- Inverter Compressor for variable capacity and economy
- high efficiency EC fan motor (indoor)
- R32 low GWP refrigerant
Cool / Heat Range kW (ISD / OSA) : 9.4 – 19.5 – 25.3 / 8.4 – 20.8 – 25.6
To view the Brochure Click here.
Description
19.5 kW Cooling
20.8 kW Heating
R32 | Variable Capacity Compressor