Mitsubishi Heavy Industries SCM40ZS-W 4.0kW Multi Split Outdoor Unit Only

SKU: SCM40ZS-W

Mitsubishi Heavy Industries SCM40ZS-W 4.0kW Multi Split System Outdoor Unit Only
Serves 2 indoor units | R32

Maximum capacity of indoor units allowed: 6.0kW



Outdoor SCM40ZS-W
Power source (Outdoor) 1 Phase 240V 50Hz
 

 

 

 

 

 

 

 

*Operation data

 

Nominal Capacity (Range)

Cooling T1  

 

kW

4.0 (1.5~5.9)
Heating H1 4.5 (1.0~6.3)
 

Power consumption

Cooling T1 0.80
Heating H1 0.83
 

Running current

Cooling T1  

A

3.4
Heating H1 3.5
Inrush current, maximum current 3.7, 14
EER Cooling T1 5.00
COP Heating H1 5.42
 

Sound power level (JIS C9612)

Cooling T1  

 

 

dB(A)

62
Heating H1 64
 

Sound pressure level (JIS C9612)

Cooling T1 49
Heating H1 51
 

Silent mode

Cooling T1 44
Heating H1 46
External dimensions (HxWxD) mm 595×780(+90)x290
Net weight  

kg

40
 

Refrigerant (R32)

Quantity 1.4
Pre charged to pipe length m 20
 

 

 

Installation data

 

Refrigerant piping

Liquid line  

mm

Ø6.35 x 2
Gas line Ø9.52 x 2
Connection method Flare connection
Maximum pipe length to one indoor unit  

m

25
Total pipe length to all indoor units 30
Max vertical height diff. between O.U. and I.U. 15 ( O.U. above I.U.) / 15 ( O.U. below I.U. )
 

 

 

 

Indoor Unit Combination

SRK-ZSA-W  

 

 

 

kW

2.0, 2.5, 3.5
SRK-ZSXA-W 2.0, 2.5, 3.5
SRK-ZRA-W
SRF-ZS(X)-W 2.5, 3.5
SRR-ZS-W 2.5, 3.5
FDTC-VH 2.5, 3.5
FDUM-VH
Indoor Unit Connection 2 Units
Indoor Connection Capacity kW 4.0 to 6.0
 

Outdoor air temperature (upper, lower limits)

Cooling °C -15 to 46
Heating -15 to 24
* Operation data are are conducted in accordance with AS/NZS 3823 standard. For testing conditions please refer to Page14.

To view the Brochure of Mitsubishi Heavy Industries Click here.

Description

4.0 kW Cooling
4.5 kW Heating

R32 | Serves 2 indoor units

air conditioning enquiry