CAPACITY | 5.0kW | |||
Set | FDTC50ZSXAWVH | |||
Indoor | FDTC50VH | |||
Outdoor | SRC50ZSXA-W | |||
Power Source (Outdoor Unit) | 1 Phase 240V 50Hz | |||
*Operation Data |
Nominal Capacity (Range) |
Cooling T1 |
kW |
5.0 (1.1 -5.6) |
Heating H1 | 5.4 (0.6-6.3) | |||
Heating H2 | 4.80 | |||
Power Consumption | Cooling T1 | 1.40 | ||
Heating H1 | 1.53 | |||
Maximum Power Consumption | 2.90 | |||
Running Current | Cooling T1 |
A |
6.2 | |
Heating H1 | 6.7 | |||
Inrush Current, Maximum Current | 5, 15 | |||
EER | Cooling T1 | 3.58 | ||
COP | Heating H1 | 3.53 | ||
Sound Power Level (JIS C9612) | Outdoor |
dB(A) |
63 | |
Sound Pressure Level (JIS C9612) |
Indoor | P-Hi:44 Hi:40 Me:35 Lo:27 | ||
Outdoor | 52 | |||
External dimensions (HXWXD) |
Indoor |
mm |
248x570x570 | |
Panel | 10X620X620 TC-PSAE-5AW-E (Honeycomb) / TC-PSAGE-5AW-E (Grid) | |||
Outdoor | 640×800(+71)x290 | |||
Net weight | Indoor | kg | Unit 14 Panel 2.5 | |
Outdoor | 45 | |||
Airflow | Cooling (Indoor) | l/s | P-Hi: 217 Hi: 183 Me: 150 Lo: 117 | |
Heating (Indoor) | ||||
Installation Data |
Refrigerant (R32) | Quantity | kg | 1.3 |
Pre-Charged to Pipe | m | 15 | ||
Refrigerant Piping | Liquid Line | mm | Ø6.35 | |
Gas Line | Ø12.7 | |||
Connection Method | Flare Connection | |||
Maximum Pipe Length (One Way) | m | 30 | ||
Max Vertical Height Diff. Between O.U. and I.U. | 20 ( O.U. above I.U. ) / 20 ( O.U. below I.U. ) | |||
Controller | RC-E5, RC-EXZ3A, RCH-E3 or RCN-TC-5AW-E2 / RCN-TC-5AW-E3 (Fine Snow) | |||
Motion Sensor (Optional) | LB-TC-5W-E | |||
Demand Response (AS4755) | Yes | |||
Outdoor air temperature (upper, lower limits) | Cooling | oC | -15 to 46 | |
Heating | -20 to 20 |
Mitsubishi Heavy Industries FDTC50ZSXAWVH 5.0kW Four Way Compact Ceiling Cassette | RC-EXZ3A Wired Controller
Mitsubishi Heavy Industries FDTC50ZSXAWVH 5.0kW Four Way Compact Ceiling Cassette
Indoor: FDTC50VH
Outdoor: SRC50ZSXA-W
Controller: RC-EXZ3A
Panel: TC-PSAE-5AW-E
Description
5.0 kW Cooling
5.4 kW Heating
Compact Cassette | R32